Brenix inspection report
142 Cedar Ridge Lane
- Inspection date
- March 14, 2026
- Inspector
- M. Alvarez, HI-48213
- Pack
- Residential Property v1.0.0
- Findings
- 6 reviewed
1
Severe
3
Moderate
2
Minor
Executive summary
This inspection identified 6 findings across roofing, structural, electrical, plumbing, and HVAC systems, ranging from minor maintenance items to one condition requiring correction before occupancy. Every finding below is rendered from a reviewed entry in the pinned Residential Property Inspection pack and remains linked to its supporting photograph and protocol item. This report was reviewed and approved by the inspector named above before delivery.
Inspection findings
Roof & Exterior
1. Roof covering — south-facing plane
ModerateCurling and granule loss were observed across multiple asphalt shingles on the south-facing roof plane, consistent with age-related wear approaching the end of serviceable life. No active leak was observed at the time of inspection.
Recommendation
Budget for roof covering replacement within 3–5 years. Monitor the attic for staining after heavy rain in the interim.
Curated source: RC-4.12 · Protocol item: roof_covering_inspection · Evidence: Photo 01, Photo 02Roof & Exterior
2. Gutters & drainage — northeast corner
MinorThe downspout at the northeast corner discharges directly at grade without an extension, directing water toward the foundation and an adjacent crawlspace vent.
Recommendation
Install a splash block or downspout extension to route water at least 6 feet from the foundation.
Photo 03Curated source: GT-2.03 · Protocol item: gutter_drainage_inspection · Evidence: Photo 03Structural
3. Foundation wall — northwest corner, basement
ModerateA vertical hairline crack measuring approximately 1.6 mm was observed in the poured concrete foundation wall in the northwest corner of the basement. No active water intrusion or efflorescence was visible at the time of inspection.
Recommendation
Monitor crack width seasonally and seal as a moisture-prevention measure. Consult a structural engineer if width increases.
Photo 04Curated source: FD-1.08 · Protocol item: foundation_wall_inspection · Evidence: Photo 04Electrical
4. Main service panel
SevereTwo double-tapped breakers were found in the main service panel, a configuration not rated for this breaker type and a recognized fire-risk condition.
Recommendation
Have a licensed electrician correct the double-tapped breakers before occupancy.
Photo 05Curated source: EL-6.01 · Protocol item: service_panel_inspection · Evidence: Photo 05Plumbing
5. Water heater — TPR valve discharge
MinorThe temperature-pressure relief valve discharge pipe terminates approximately 8 inches above the floor, exceeding the 6-inch maximum typically required.
Recommendation
Adjust the discharge pipe termination height to comply with local code.
Photo 06Curated source: PL-3.14 · Protocol item: water_heater_inspection · Evidence: Photo 06HVAC
6. Furnace — condition and service life
ModerateThe furnace filter was visibly clogged, restricting airflow. The unit's manufacture label indicates an age of approximately 16 years, near the end of typical service life for this equipment type.
Recommendation
Replace the filter immediately and begin budgeting for system replacement planning.
Photo 07Curated source: HV-5.02 · Protocol item: furnace_inspection · Evidence: Photo 07
Source references
- RC-4.12
- Roof covering — south-facing plane
- GT-2.03
- Gutters & drainage — northeast corner
- FD-1.08
- Foundation wall — northwest corner, basement
- EL-6.01
- Main service panel
- PL-3.14
- Water heater — TPR valve discharge
- HV-5.02
- Furnace — condition and service life
Inspector approval
Every finding above was reviewed, edited where necessary, and explicitly approved by the inspector of record before this report was made available for delivery.
M. Alvarez
Licensed Home Inspector · HI-48213