Brenix inspection report

142 Cedar Ridge Lane

142 Cedar Ridge Lane, Maplewood Heights, MI 48213

Inspection date
March 14, 2026
Inspector
M. Alvarez, HI-48213
Pack
Residential Property v1.0.0
Findings
18 of 18 reviewed
Sample · illustrative

2

Severe

9

Moderate

7

Minor

About this report

How this report was produced

    Step 1

    Evidence captured in the field

    Photographs, measurements, and field notes were captured on site and time-stamped at the point of capture. Each item carries a content hash recorded at upload.

    Step 2

    Findings drafted against a pinned protocol pack

    Each observation was matched to an item in the Residential Property v1.0.0 pack. The pack version is fixed for the life of this report.

    Step 3

    Every finding traced to its source

    No finding appears without a linked evidence item and a curated source reference. Ungrounded statements were withheld rather than inferred.

    Step 4

    Inspector review and approval

    The inspector of record reviewed, edited where necessary, and explicitly approved every drafted finding before release.

Executive summary

18 findings across six systems

Two conditions are rated Severe and require correction before occupancy. Nine are rated Moderate and should be corrected within a defined period. Seven are rated Minor and represent routine maintenance or baseline observations. F-15 records combustion spillage from a separated furnace flue joint; the furnace should not be operated until corrected. F-08 records double-tapped breakers in the main service panel, a recognised fire-risk configuration.

SystemSevereModerateMinorTotal
Roof & Exterior0224
Structural0213
Electrical1113
Plumbing0123
HVAC1203
Insulation & Ventilation0112
All systems29718

Priority actions

IDFindingReferralTiming
F-15Separated furnace flue vent connectorHVAC contractorImmediate
F-08Double-tapped breakers in service panelLicensed electricianBefore occupancy
F-09Absent GFCI protection at wet locationsLicensed electrician30 days
F-18Bath exhaust terminating in atticHVAC or general contractor60 days
F-06Floor joist notched beyond allowable depthContractor or engineer90 days
F-13S-trap at kitchen sink drainPlumber90 days
F-16Disconnected supply duct in crawlspaceHVAC contractor90 days
F-03Deteriorated chimney base flashingRoofing contractorBefore winter
F-01Roof covering near end of lifeRoofing contractor3 to 5 years

Scope and limitations

What was and wasn't inspected

Roof covering, flashings and penetrationsInspectedFrom ground and roof edge
Gutters, downspouts and surface drainageInspectedFull perimeter
Exterior cladding, trim and openingsInspectedAll elevations
Foundation, basement and crawlspaceInspectedFull access obtained
Floor, wall and roof framingInspectedWhere visible
Electrical service, panel and distributionInspectedPanel cover removed
Receptacles, switches and fixturesInspectedRepresentative sample
Water supply, distribution and fixturesInspectedAll accessible
Drain, waste and vent pipingInspectedWhere visible
Water heating equipmentInspectedOperated
Heating equipment and distributionInspectedOperated
Cooling equipmentNot inspectedOutside operating temperature range
Insulation and ventilationInspectedAttic and crawlspace
Interior surfaces, doors and windowsInspectedRepresentative sample
Attached garage and vehicle doorInspectedAuto-reverse tested
Fireplace and solid fuel appliancesNot inspectedNone present
Private water or septic systemsNot inspectedMunicipal service
Swimming pool or spaNot inspectedNone present
Detached structuresNot inspectedNone present
Environmental hazards, pests, mould testingExcludedOutside scope of engagement
Weather
Overcast, dry; 46°F
Occupancy
Vacant, furnished
Ground condition
Dry
Utilities on
Water, gas, electric

Inspection findings

Every finding, grouped by system

Roof & Exterior

  1. F-01 · South-facing roof plane

    Roof covering approaching end of serviceable life

    Moderate

    Observation

    Curling and granule loss were observed across a majority of asphalt shingles on the south-facing roof plane. Granule accumulation was present in the gutter trough below. Shingle edges lifted under light hand pressure at three sampled locations. No active leak, interior staining, or daylight penetration was observed at the time of inspection.

    Why it matters

    Granule loss exposes the asphalt mat to ultraviolet degradation, which accelerates further deterioration. The south-facing plane receives the greatest solar load and typically fails first. Remaining service life is estimated at three to five years under normal weather conditions.

    Recommendation

    Budget for full roof covering replacement within three to five years. Monitor the attic for staining after heavy rainfall in the interim. Obtain a roofing contractor evaluation before the next winter season.

    Referral: Roofing contractor

    P-01P-02P-03
    Curated source: RC-4.12 · Protocol item: roof_covering_inspection
  2. F-02 · Northeast corner, exterior

    Downspout discharges at grade adjacent to foundation

    Minor

    Observation

    The downspout at the northeast corner terminates directly at grade with no extension or splash block. Soil erosion was visible in a shallow channel running toward the foundation wall. An adjacent crawlspace vent sits approximately 18 inches from the discharge point.

    Why it matters

    Concentrated roof runoff discharging at the foundation is a common contributor to hydrostatic pressure, foundation movement, and crawlspace moisture. The proximity of the crawlspace vent creates a direct path for water entry during heavy rainfall.

    Recommendation

    Install a splash block or downspout extension routing discharge a minimum of six feet from the foundation. Regrade the eroded channel to maintain positive drainage away from the structure.

    Referral: Owner maintenance

    P-04
    Curated source: GT-2.03 · Protocol item: gutter_drainage_inspection
  3. F-03 · Chimney base, north roof plane

    Deteriorated sealant at chimney base flashing

    Moderate

    Observation

    The counter-flashing at the chimney base shows separated and cracked sealant along the north and east faces. A gap of approximately 4 mm was measured at the northeast corner. Minor rust staining was present on the step flashing below.

    Why it matters

    Chimney flashing is among the most frequent points of roof water entry. Separated sealant permits water to track behind the counter-flashing and into the roof structure, where damage can progress without visible interior evidence for extended periods.

    Recommendation

    Have the counter-flashing resealed by a qualified roofing contractor. Inspect the attic sheathing adjacent to the chimney chase for staining during the same visit.

    Referral: Roofing contractor

    P-05P-06
    Curated source: FL-4.21 · Protocol item: chimney_flashing_inspection
  4. F-04 · South elevation, near grade

    Impact damage to vinyl cladding

    Minor

    Observation

    Two vinyl siding panels on the south elevation show cracking consistent with impact damage, located approximately 30 inches above grade near the driveway. The weather-resistive barrier behind the damaged panels appeared intact where visible through the cracks.

    Why it matters

    Cracked cladding permits wind-driven rain to reach the weather-resistive barrier and sheathing. The condition is cosmetic in the near term but will admit moisture over time.

    Recommendation

    Replace the two damaged panels. Vinyl siding panels can be individually removed and replaced without disturbing surrounding courses.

    Referral: Owner maintenance

    P-07
    Curated source: EX-7.09 · Protocol item: cladding_inspection

Structural

  1. F-05 · Northwest corner, basement

    Vertical hairline crack in poured foundation wall

    Moderate

    Observation

    A vertical crack measuring approximately 1.6 mm at its widest point was observed in the poured concrete foundation wall at the northwest corner of the basement, extending from approximately 14 inches below the sill plate to within 8 inches of the slab. No lateral displacement was measured across the crack. No efflorescence, staining, or active water intrusion was visible at the time of inspection.

    Why it matters

    Vertical cracks of this width in poured foundations are commonly associated with concrete shrinkage during curing and are not typically structural. However, width change over time is the indicator that distinguishes shrinkage cracking from active movement, and that determination requires monitoring rather than a single observation.

    Recommendation

    Record the crack width at the widest point and re-measure seasonally. Seal with a flexible polyurethane or epoxy injection as a moisture-prevention measure. Engage a licensed structural engineer if width increases beyond 3 mm or if lateral displacement develops.

    Referral: Monitor; structural engineer if progressive

    P-08P-09
    Curated source: FD-1.08 · Protocol item: foundation_wall_inspection
  2. F-06 · Crawlspace, central bay

    Floor joist notched beyond allowable depth

    Moderate

    Observation

    A 2x10 floor joist in the central crawlspace bay has been notched on its lower edge to approximately 4 inches depth to accommodate a drain line. The notch is located near mid-span. No sag, splitting, or deflection was measured at the time of inspection.

    Why it matters

    Notching the tension edge of a joist near mid-span removes a disproportionate share of its bending capacity. Conventional framing practice limits notch depth and prohibits notching in the middle third of the span entirely. The condition reduces the joist's factored capacity and may allow deflection to develop under sustained load.

    Recommendation

    Have the joist evaluated and reinforced by a qualified contractor. Sistering a full-length member alongside the notched joist is the customary remedy.

    Referral: General contractor or structural engineer

    P-10P-11
    Curated source: FR-1.22 · Protocol item: floor_framing_inspection
  3. F-07 · Attic, above main bedroom

    Minor rafter deflection, no active movement

    Minor

    Observation

    Slight deflection was observed in two rafters above the main bedroom, estimated at under 1/2 inch across the span. Collar ties are present and fastened. No cracking, splitting, or bearing displacement was observed. Sheathing above the affected rafters was sound with no delamination.

    Why it matters

    Deflection of this magnitude in a roof structure of this age is typically long-standing and non-progressive. It is recorded here as a baseline observation rather than a defect requiring correction.

    Recommendation

    No action required. Re-observe at the next inspection interval to confirm the condition remains static.

    Referral: None

    P-12
    Curated source: FR-1.44 · Protocol item: roof_structure_inspection

Electrical

  1. F-08 · Main service panel, basement

    Double-tapped breakers in main service panel

    Severe

    Observation

    Two circuit breakers in the main service panel were found with two conductors terminated under a single breaker lug. The breakers in question are not listed for multiple conductor termination. The affected breakers serve the kitchen small-appliance circuit and a basement lighting circuit.

    Why it matters

    A breaker lug not rated for two conductors cannot reliably maintain clamping force on both. The resulting loose connection generates heat under load, and this configuration is a recognised cause of panel fires. The condition is present on a circuit that regularly carries substantial load.

    Recommendation

    Have a licensed electrician correct both double-tapped connections before occupancy. Correction typically involves installing additional breakers or an approved pigtail connection. This item should be treated as a pre-occupancy correction rather than deferred maintenance.

    Referral: Licensed electrician — before occupancy

    P-13P-14
    Curated source: EL-6.01 · Protocol item: service_panel_inspection
  2. F-09 · Kitchen and both bathrooms

    Absent GFCI protection at wet-location receptacles

    Moderate

    Observation

    Receptacles serving the kitchen counter (three locations), the main bathroom vanity, and the basement bathroom vanity tested without ground-fault circuit interrupter protection. Testing was performed with a plug-in GFCI tester at each location.

    Why it matters

    GFCI protection interrupts current on detection of a ground fault, and its absence at wet locations removes the primary protection against electrocution in the areas where that risk is highest. This is a life-safety provision rather than a code-compliance formality.

    Recommendation

    Have a licensed electrician install GFCI protection at all kitchen counter and bathroom receptacles. Protection may be provided at the receptacle or at the breaker.

    Referral: Licensed electrician

    P-15P-16
    Curated source: EL-6.18 · Protocol item: gfci_protection_inspection
  3. F-10 · Rear exterior wall

    Missing weatherproof cover at exterior receptacle

    Minor

    Observation

    The exterior receptacle on the rear wall adjacent to the patio door is missing its weatherproof in-use cover. The receptacle itself is GFCI-protected and tested correctly. Minor corrosion was visible on the mounting strap.

    Why it matters

    An uncovered exterior receptacle admits moisture to the device and box, which promotes corrosion and can eventually defeat the GFCI device it depends on for protection.

    Recommendation

    Install a listed weatherproof in-use cover. This is a low-cost owner-serviceable item.

    Referral: Owner maintenance

    P-17
    Curated source: EL-6.33 · Protocol item: exterior_receptacle_inspection

Plumbing

  1. F-11 · Water heater, basement utility room

    TPR discharge pipe terminates above required height

    Minor

    Observation

    The temperature-pressure relief valve discharge pipe terminates approximately 8 inches above the floor. The customary maximum termination height is 6 inches. The pipe is correctly sized, is of approved material, and runs downward without traps.

    Why it matters

    A discharge pipe terminating too high above the floor increases the risk of scalding spray reaching a person standing nearby during a relief event. The remainder of the installation is correct.

    Recommendation

    Extend the discharge pipe to terminate between 2 and 6 inches above the floor.

    Referral: Plumber or owner maintenance

    P-18
    Curated source: PL-3.14 · Protocol item: water_heater_inspection
  2. F-12 · Basement, main supply entry

    Corrosion at main supply shutoff valve

    Minor

    Observation

    Green corrosion product was observed at the packing nut of the main water supply shutoff valve. The valve body is dry, and no active drip was observed during a 20-minute observation period. The valve was not operated during the inspection.

    Why it matters

    Corrosion at the packing nut indicates a past or intermittent weep. Gate valves of this age commonly fail to seat fully when operated after long periods of inactivity, which can leave a property without a functioning main shutoff during an emergency.

    Recommendation

    Have a plumber evaluate and, if appropriate, replace the valve with a quarter-turn ball valve. Confirm the valve fully closes as part of the same visit.

    Referral: Plumber

    P-19
    Curated source: PL-3.02 · Protocol item: supply_piping_inspection
  3. F-13 · Kitchen sink cabinet

    S-trap configuration at kitchen sink drain

    Moderate

    Observation

    The kitchen sink drain is configured as an S-trap, with the trap arm turning vertically downward without an intervening vent connection. No vent was visible within the cabinet.

    Why it matters

    An S-trap is prone to siphoning its own water seal as waste discharges, which allows sewer gas to enter the living space. The condition is intermittent by nature and may not be apparent to occupants until the seal is lost.

    Recommendation

    Have a plumber reconfigure the drain to a P-trap with proper venting, or install a listed air admittance valve where local practice permits.

    Referral: Plumber

    P-20
    Curated source: PL-3.27 · Protocol item: drain_waste_vent_inspection

HVAC

  1. F-14 · Furnace, basement utility room

    Furnace near end of service life; filter restricted

    Moderate

    Observation

    The furnace filter was visibly clogged with dust and lint, substantially restricting airflow. The unit's manufacturer data plate indicates a manufacture date of 2010, giving an approximate age of 16 years. The heat exchanger was not accessible for direct visual inspection. The unit responded to thermostat call and produced heat during the inspection.

    Why it matters

    A restricted filter reduces airflow across the heat exchanger, which raises operating temperatures and shortens equipment life. At 16 years the unit is at or near the end of typical service life for forced-air furnaces, and the heat exchanger condition cannot be confirmed without disassembly.

    Recommendation

    Replace the filter immediately and establish a quarterly replacement schedule. Have the unit serviced by an HVAC contractor including a heat exchanger evaluation. Begin budget planning for replacement.

    Referral: HVAC contractor

    P-21P-22
    Curated source: HV-5.02 · Protocol item: furnace_inspection
  2. F-15 · Furnace flue, basement

    Separated joint in furnace flue vent connector

    Severe

    Observation

    The single-wall metal vent connector between the furnace and the chimney thimble is separated at the second joint from the appliance. A visible gap of approximately 10 mm is present around the full circumference. No fasteners were present at the joint. Light soot deposits were observed on the surface below the separation.

    Why it matters

    A separated flue vent connector permits combustion products, including carbon monoxide, to spill into the occupied basement rather than venting to the exterior. Soot deposits indicate that spillage has already occurred. This is an immediate life-safety condition.

    Recommendation

    Do not operate the furnace until the vent connector has been repaired. Have an HVAC contractor reassemble and fasten the connector, and verify draft under operating conditions. Install carbon monoxide alarms on each level if not already present.

    Referral: HVAC contractor — immediate; do not operate until corrected

    P-23P-24
    Curated source: HV-5.19 · Protocol item: combustion_venting_inspection
  3. F-16 · Crawlspace, west run

    Disconnected supply duct in crawlspace

    Moderate

    Observation

    A flexible supply duct serving the west bedroom is disconnected at the plenum takeoff and is discharging conditioned air into the crawlspace. The duct is otherwise intact and insulated.

    Why it matters

    Conditioned air discharged into a crawlspace is entirely lost, raising energy cost and leaving the served room under-conditioned. Positive pressure in the crawlspace also drives moisture-laden air into the floor assembly.

    Recommendation

    Have the duct reconnected and secured at the takeoff with a mechanical fastener and mastic. Inspect remaining crawlspace duct connections during the same visit.

    Referral: HVAC contractor

    P-25
    Curated source: HV-5.31 · Protocol item: duct_distribution_inspection

Insulation & Ventilation

  1. F-17 · Attic, general

    Attic insulation below current recommended depth

    Minor

    Observation

    Blown cellulose insulation in the attic measures between 5 and 7 inches in depth across sampled locations, corresponding to approximately R-20. Coverage is uneven, with thin areas at the perimeter above the top plates. Baffles are present at the eaves and are unobstructed.

    Why it matters

    Insulation depth below current recommendations increases heating and cooling cost and contributes to uneven interior temperatures. It is an efficiency consideration rather than a safety or structural one.

    Recommendation

    Consider supplementing to approximately R-49 for this climate zone. Prioritise the perimeter areas where depth is lowest. Confirm baffles remain unobstructed after any addition.

    Referral: Insulation contractor — discretionary

    P-26
    Curated source: IN-8.04 · Protocol item: attic_insulation_inspection
  2. F-18 · Attic, above main bathroom

    Bathroom exhaust fan terminates within attic space

    Moderate

    Observation

    The main bathroom exhaust fan duct terminates inside the attic space rather than at an exterior termination. Moisture staining and light mould growth were observed on the sheathing within approximately three feet of the duct outlet.

    Why it matters

    Discharging humid air into an unconditioned attic condenses moisture on cold sheathing, producing the staining and growth observed. Continued operation will progressively damage the sheathing and may affect insulation performance.

    Recommendation

    Extend the duct to a dedicated roof or gable exterior termination with a backdraft damper. Have the affected sheathing evaluated and treated. Confirm the fan achieves adequate flow after modification.

    Referral: HVAC or general contractor

    P-27P-28
    Curated source: IN-8.22 · Protocol item: exhaust_ventilation_inspection

Evidence index

Every photograph, timestamped and hashed

Hashes are truncated for display; full values are retained in the platform record and can be verified against the original file.

RefCapturedSubjectFinding
P-0109:14:22Roof, south planeF-01
P-0209:15:07Roof, south plane detailF-01
P-0309:16:44Gutter trough, granule accumulationF-01
P-0409:22:10Downspout, northeast cornerF-02
P-0509:31:55Chimney base flashing, north faceF-03
P-0609:32:31Chimney flashing, northeast gapF-03
P-0709:41:18South elevation cladding damageF-04
P-0810:03:47Basement northwest foundation wallF-05
P-0910:04:26Crack width measurementF-05
P-1010:19:02Crawlspace joist notchF-06
P-1110:19:48Notch depth measurementF-06
P-1210:38:15Attic rafters above main bedroomF-07
P-1310:52:39Main service panel, cover removedF-08
P-1410:53:12Double-tapped breaker detailF-08
P-1511:07:24Kitchen counter receptacle testF-09
P-1611:11:03Main bath vanity receptacle testF-09
P-1711:19:50Rear exterior receptacleF-10
P-1811:33:41Water heater TPR dischargeF-11
P-1911:36:19Main supply shutoff valveF-12
P-2011:48:56Kitchen sink drain configurationF-13
P-2112:02:11Furnace data plateF-14
P-2212:03:04Furnace filter conditionF-14
P-2312:07:38Flue vent connector separationF-15
P-2412:08:22Soot deposits below connectorF-15
P-2512:21:47Crawlspace disconnected supply ductF-16
P-2612:35:09Attic insulation depth measurementF-17
P-2712:39:52Bath exhaust duct terminationF-18
P-2812:40:31Sheathing staining near outletF-18

Source references

Each finding cites a curated source reference from the pinned protocol pack, fixed for the life of this report so the basis of every finding remains reproducible after the pack is revised.

RC-4.12
Roof covering approaching end of serviceable life
GT-2.03
Downspout discharges at grade adjacent to foundation
FL-4.21
Deteriorated sealant at chimney base flashing
EX-7.09
Impact damage to vinyl cladding
FD-1.08
Vertical hairline crack in poured foundation wall
FR-1.22
Floor joist notched beyond allowable depth
FR-1.44
Minor rafter deflection, no active movement
EL-6.01
Double-tapped breakers in main service panel
EL-6.18
Absent GFCI protection at wet-location receptacles
EL-6.33
Missing weatherproof cover at exterior receptacle
PL-3.14
TPR discharge pipe terminates above required height
PL-3.02
Corrosion at main supply shutoff valve
PL-3.27
S-trap configuration at kitchen sink drain
HV-5.02
Furnace near end of service life; filter restricted
HV-5.19
Separated joint in furnace flue vent connector
HV-5.31
Disconnected supply duct in crawlspace
IN-8.04
Attic insulation below current recommended depth
IN-8.22
Bathroom exhaust fan terminates within attic space

Review and audit trail

What the inspector changed, and when

Findings not listed below were accepted as drafted with no edits.

FindingReview actionEditsApproved
F-01Accepted as drafted014:02
F-02Accepted as drafted014:02
F-03Edited — recommendation expanded114:03
F-05Edited — measurement corrected214:05
F-06Edited — referral added114:06
F-08Edited — severity confirmed, wording tightened114:09
F-09Accepted as drafted014:10
F-13Edited — remedy options added114:13
F-15Edited — do-not-operate instruction added214:17
F-18Accepted as drafted014:19
Findings drafted
18
Findings edited
7
Evidence items linked
28
Review duration
38 minutes

Inspector approval

Every finding above was reviewed, edited where necessary, and explicitly approved by the inspector of record before this report was made available for delivery. The inspector of record is accountable for the content of this report.

M. Alvarez

Licensed Home Inspector · HI-48213

Approved · March 14, 2026